RJCSR1A23D30EPPO CARLO GAVAZZI, RJCSR1A23D30EPPO Datasheet

SSR, DIN RAIL MOUNT, 265VAC, 32VDC, 30A

RJCSR1A23D30EPPO

Manufacturer Part Number
RJCSR1A23D30EPPO
Description
SSR, DIN RAIL MOUNT, 265VAC, 32VDC, 30A
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of RJCSR1A23D30EPPO

Control Voltage Type
DC
Control Voltage Range
4VDC To 32VDC
Operating Voltage Range
24VAC To 265VAC
Peak Surge Current
600A
Contact Configuration
SPST
Load Current
30A
Specifications are subject to change without notice (05.07.2007)
Selection Guide
Options
-
Auto-
ranging
Solid State Relays
SOLITRON MIDI Current Sensing
Type RJCS, RJCSR
Product Description
The SOLITRON Midi Current
Sensing is a compact, single-
phase SSR that is sensitive to
variations in load conditions in
industrial heating applications.
This
device is ideal for detection of
partial load failure and to
ensure the highest process
quality. Current sensing is inte-
grated inside to eliminate the
need to install an external cur-
rent transformer. A membrane
“button” on the front is used to
effect a simple “teach in” of the
current setpoint. Alarm delay
time is set by a potentiometer.
A drop in setpoint current of
more than 13% will trigger an
Type Selection
Options
R:Autoranging A: Zero switching
microprocessor-based
Rated
operational
voltage
230 VACrms
600 VACrms
230 VACrms
600 VACrms
Switching
mode
Blocking
voltage
650 Vp
1200 Vp
650 Vp
1200 Vp
Rated
operational
voltage
23: 230 VACrms D: 4 - 32 VDC 30: 30 AACrms
60: 600 VACrms
open collector alarm.
Up to 50 alarm outputs can be
connected in parallel to a stan-
dard PLC input. Typical condi-
tions that can be detected are
heater break or open-circuit,
blown fuse, semiconductor
short-circuit and faulty power
connection.
Device over-temperature pro-
tection is integrated as a stan-
dard feature.
The product is ready to mount
on DIN-rail or chassis and
comes with integral heatsink.
The standard housing dimen-
sions enable straightforward
replacement
products.
Control
voltage
4 - 32 VDC
4 - 32 VDC
4 - 32 VDC
4 - 32 VDC
Control
voltage
of
alternative
Supply
voltage
24 VDC
24 VDC
24 VDC
24 VDC
Rated
operational
current
50: 50 AACrms
• AC semiconductor contactor
• Integrated current monitoring
• Zero switching
• Direct copper bonding (DCB) technology
• LED-indication
• Cage clamp output terminals
• 4-32 VDC control input
• Operational ratings up to 50 AACrms and 600 VAC
• Local and remote alarm status
• Set-point adjustable
• Time delay adjustable
• Local and remote setup
Ordering Key
Solid State Relay
Current Sensing
Autoranging (option)
Number of poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Terminal layout
Over-temperature protection
Alarm output type
Alarm
output
type
NPN, NO
PNP, NO
NPN, NO
PNP NO
NPN, NO
PNP, NO
NPN, NO
PNP NO
Terminal
layout
E: Contactor
Rated operational
current
30 A
-
-
-
-
RJCSR1A23D30EPNO RJCSR1A23D50EPNO
RJCSR1A23D30EPPO RJCSR1A23D50EPPO
RJCSR1A60D30EPNO RJCSR1A60D50EPNO
RJCSR1A60D30EPPO RJCSR1A60D50EPPO
RJ CS R 1 A 60 D 50 E P NO
Protection
P: Over-temp.
protection
50A
RJCS1A23D50EPNO
RJCS1A23D50EPPO
RJCS1A60D50EPNO
RJCS1A60D50EPPO
Alarm output
type
NO: NPN, Normally open
PO: PNP , Normally open
1

Related parts for RJCSR1A23D30EPPO

RJCSR1A23D30EPPO Summary of contents

Page 1

... PNP VDC 24 VDC NPN, NO PNP VDC 24 VDC NPN, NO PNP Terminal Protection Alarm output layout type E: Contactor P: Over-temp. NO: NPN, Normally open protection PO: PNP , Normally open Rated operational current 30 A 50A - RJCS1A23D50EPNO - RJCS1A23D50EPPO - RJCS1A60D50EPNO - RJCS1A60D50EPPO RJCSR1A23D30EPNO RJCSR1A23D50EPNO RJCSR1A23D30EPPO RJCSR1A23D50EPPO RJCSR1A60D30EPNO RJCSR1A60D50EPNO RJCSR1A60D30EPPO RJCSR1A60D50EPPO 1 ...

Page 2

RJCS General Specifications Operational voltage range Blocking voltage Operational frequency range Power factor Approvals CE-marking Supply status indication Control status indication Over-temperature alarm trip indication Alarm indication (excpect for over-temperature trip) Input Specifications Control voltage range Pick-up voltage Reverse voltage ...

Page 3

RJCS Output Specifications Rated operational current AC51 @Ta=25ºC Measuring range Min. TEACH current Min. partial load current Non rep. surge current (t=10ms) Off-state leakage current @rated voltage and frequency for fusing ( ms) On-state voltage ...

Page 4

RJCS Alarm Operation 1.1 Current Setpoint the device will return to nor- The current setpoint is the mal operation. If the alarm nominal operating current that condition is still active, the is expected when all the heater device will automatically ...

Page 5

RJCS Example Let the alarm delay setting be than 2s. (Any fluctutation in 2s (min). If the full load current the load current that is pre- is set at 30A, then there will be sent for <2s will not be ...

Page 6

RJCS Derating vs. Spacing Curves Note: Based on 100% duty cycle Note: Based on 100% duty cycle 6 Surrounding temp. (˚C) Surrounding temp. (˚C) Specifications are subject to change without notice (05.07.2007) RJCS......30.... RJCS......50.... ...

Page 7

RJCS Setup and Alarms Current under-range detected during TEACH Heater break alarm Note: Above shows pulses for PNP device Specifications are subject to change without notice (05.07.2007) 7 ...