LC2D12F7 SQUARE D, LC2D12F7 Datasheet - Page 3

no-image

LC2D12F7

Manufacturer Part Number
LC2D12F7
Description
Contactor
Manufacturer
SQUARE D
Datasheet

Specifications of LC2D12F7

No. Of Poles
3
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
110V
Contact Voltage Ac Max
600V
Nom Operating Power
7.5kW
Contact Voltage Ac Nom
690V
Contact Current Ac Max
25A
Contact Current Max
12A
Coil Type
AC
Operating Voltage
600VAC
Switching Power Ac1
2hp
Switching Power Ac3
10hp
Switching Current Ac1
25A
Switching Current Ac3
12A
Load Current Inductive
12A
Load Current Resistive
25A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Complementary
Environment
Offer Sustainability
Coil technology
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non-overlap time
Insulation resistance
IP degree of protection
Protective treatment
Pollution degree
Ambient air temperature for operation
Ambient air temperature for storage
Permissible ambient air temperature around the de-
vice
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
Height
Width
Depth
Product weight
Sustainable offer status
RoHS
Product environmental profile
Product end of life instruction
Safety reliability level
Mechanical durability
Operating rate
Without built-in suppressor module
0.85...1.1 Uc at 60 °C operational 60 Hz
0.8...1.1 Uc at 60 °C operational 50 Hz
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
2...3 W at 50/60 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
25...400 Hz
5 mA for signalling circuit
17 V for signalling circuit
1.5 ms on energisation (between NC and NO contact)
1.5 ms on de-energisation (between NC and NO contact)
> 10 MOhm for signalling circuit
IP2x front face conforming to IEC 60529
TH conforming to IEC 60068-2-30
3
-5...60 °C
-60...80 °C
-40...70 °C at Uc
3000 m without derating in temperature
850 °C conforming to IEC 60695-2-1
V1 conforming to UL 94
Shocks contactor closed 15 Gn for 11 ms
Shocks contactor open 10 Gn for 11 ms
Vibrations contactor closed 4 Gn, 5...300 Hz
Vibrations contactor open 2 Gn, 5...300 Hz
77 mm
90 mm
86 mm
0.697 kg
Not Green Premium product
Compliant - since 0627 - Schneider Electric declaration of conformity
declaration of conformity
Available
Need no specific recycling operations
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
15 Mcycles
3600 cyc/h at <= 60 °C