AA-100-24-44-00-XX Laird Technologies, AA-100-24-44-00-XX Datasheet - Page 2

THERMOELECTRIC ASSY AIR-AIR 5.6A

AA-100-24-44-00-XX

Manufacturer Part Number
AA-100-24-44-00-XX
Description
THERMOELECTRIC ASSY AIR-AIR 5.6A
Manufacturer
Laird Technologies
Series
AAr
Datasheet

Specifications of AA-100-24-44-00-XX

Heat Transfer Type
Air to Air
Power - Cooling
102W
Current
5.6A
Voltage
24V
Fan Location
Cold Side / Warm Side
Operating Temperature
-20°C ~ 55°C
Weight
9.0 lbs (4.08kg)
Dimensions - Overall
300mm L x 152mm W x 161mm H
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Power - Input
-
Other names
926-1044
Innovative Technology
for a Connected World
SpECiFiCATiONS
Technical
Technology
Cooling at dT = 0°C, and nominal / float voltage.
Heating
Voltage (nominal / maximum)
Grounding (all voltages)
Current draw, ±10%
(nominal / startup)
Dimensions, cold side (L
Dimensions, warm side (L
Weight
Panel mounting
Fan life (L
Number of connectors (with / without controller)
Connector type
(on unit / mating side)
Hi-pot testing
Environmental
Temperature range
Temperature range (internal enclosure)
Degree of protection, enclosure
Degree of protection, unit
Sound level (1m distance)
Controllers (optional)
LK-81 – Thermostatic control (solid state)
LK-81 – Low Voltage Disconnect /
Re-connect (LVD / LVD-R)
LK-81 – Regulation
Ordering codes
24V, without controller
24V, with controller
48V, without controller
48V, with controller
1)
2)
3)
4)
5)
Note: The specified performance of any Laird Technologies cooling unit is dependent on how it is handled and incorporated into the final product. This includes elements such
THR-DS-TEA 0610
Any information furnished by Laird Technologies, Inc. and its agents is believed to be accurate and reliable. All specifications are subject to change without notice. Responsibility for the use and application of Laird Technologies materials rests
with the end user, since Laird Technologies and its agents cannot be aware of all potential uses. Laird Technologies makes no warranties as to the fitness, merchantability or suitability of any Laird Technologies materials or products for any
specific or general uses. Laird Technologies shall not be liable for incidental or consequential damages of any kind. All Laird Technologies products are sold pursuant to the Laird Technologies’ Terms and Conditions of sale in effect from time
to time, a copy of which will be furnished upon request. © Copyright 2010 Laird Technologies, Inc. All Rights Reserved. Laird, Laird Technologies, the Laird Technologies Logo, and other marks are trade marks or registered trade marks of Laird
Technologies, Inc. or an affiliate company thereof. Other product or service names may be the property of third parties. Nothing herein provides a license under any Laird Technologies or any third party intellectual property rights.
Cooling capacities at nominal / float voltage are rated at external temperatures of 32°C and 46°C respectively. Float voltage is defined as 27 and 54 VDC.
Heating capacity is rated at external temperature of -40°C, nominal voltage, and dT = -45°C.
Controller function shall not operate the external fan during heating mode.
The highest environmental protection level requires an external shroud and is defined as the protection level for the enclosure.
Rating for unit without protective shroud.
as the system design, insulation design, and assembly method. While Laird Technologies is able to provide general guidelines based upon our experience, it is ultimately
the responsibility of the device manufacturer to validate each product and its performance for its intended use.
2
10
at +40°C)
3
(external ambient)
C
x W
W
5
x W
C
x H
W
4
x H
C
)
Outdoor Thermoelectric Cooler Assemblies
W
)
1
AA-100-…
102/113W (348/386 Btu/h)
125W (427 Btu/h)
24/28 VDC 48/56 VDC
5.6/7.2 A (24V version)
2.8/3.6 A (48V version)
230 x 122 x 83 mm (9.1 x 4.8 x 3.3 in)
300 x 152 x 78 mm (11.8 x 6.0 x 3.1 in)
4.1 kg (9.0 lbs)
58 dB(A)
AA-100-24-44-00-XX
AA-100-48-44-00-XX
Thermoelectric (TE) modules, forced air, closed loop (non-mixing), filterless, non-refrigerant
AA-100 / AA-150 / AA-200
On unit: AMP part number: 350777-1, 794269, 350547-6, 794270-1
Mating side: AMP part number : 350778-1, 350550-6, 794270-1
Heating, set point 10°C (50°F), +/- 2°C (3.5°F)
Cooling, set point 25°C (77°F), +/- 2°C (3.5°F)
50.2 / 51.4V, +/- 0.5V (48 VDC version A)
47.0 / 49.0V, +/- 0.5V (48 VDC version B)
AA-150-…
143/159W (488/543 Btu/h)
150W (512 Btu/h)
24/28 VDC 48/56 VDC
7.9/10.0 A (24V version)
3.9/5.0 A (48V version)
250 x 152 x 83 mm (9.8 x 6.0 x 3.3 in)
300 x 180 x 84 mm (11.8 x 7.1 x 3.3 in)
5.1 kg (11.2 lbs)
58 dB(A)
25.0 / 26.0V, +/- 0.5V (24 VDC versions)
AA-150-24-44-00-XX
AA-150-24-44-LK-XX
AA-150-48-44-00-XX
AA-150-48-44-LK-XX
-40°C to +55°C (-40°F to +131°F)
-20°C to +55°C (-4°F to +131°F)
Positive or negative
≥70,000 hours
NEMA 4 (IP55)
707 VDC
Through
ON/OFF
IP54
1/3
AA-200-…
193/214W (659/731 Btu/h)
250W (853 Btu/h)
24/28 VDC 48/56 VDC
11.3/14.3 A (24V version)
5.6/7.2 A (48V version)
350 x 152 x 89 mm (13.8 x 6.0 x 3.5 in)
400 x 180 x 89 mm (15.7 x 7.1 x 3.5 in)
6.6 kg (14.5 lbs)
63 dB(A)
AA-200-24-44-00-XX
AA-200-24-44-LK-XX
AA-200-48-44-00-XX
AA-200-48-44-LK-XX